All-Aluminum Compact Stranded Conductor

A1 (ASC), ALUMINUM  CONDUCTOR,COMPACT-LAY-STRANDED (MECHANICAL PROPERTIES)
CODE WORD
CSA DESIGNATION
CONDUCTOR SIZE STRANDING NO. X DIA (mm)
CLASS  O.D.(mm)
NOMINAL MASS KG/KM
RATED STRENGTH
kN
AWG OR kcmil
mm2
Toad 13-A1F-7-4.3 #6 13.3 7x1.56 A 4.28 36.58 2.61
Dragon 21-A1F-7-5.4 #4 21.2 7x1.96 A 5.41 57.74 4.12
Molcch 34-A1F-7-6.8 #2 33.6 7x2.47 AA 6.81 91.70 6.21
Monitor 42-A1F-7-7.6 #1 42.4 7x2.78 AA 7.59 116.2 7.44
Newt 42-A1F-18-7.6 #1 42.4 18x1.73 A 7.59 116.6 8.25
Tuatara 54-A1F-7-8.5 1/0 53.5 7x3.12 AA 8.53 146.3 9.10
Skink 54-A1F-18-8.6 1/0 53.5 18x1.95 A 8.55 148.2 10.5
Alligator 67-A1F-7-9.6 2/0 67.4 7x3.50 AA 9.55 184.1 11.4
Gecko 67-A1F-18-9.6 2/0 67.4 18x2.18 A 9.55 185.2 12.8
Crccodile 85-A1F-7-10.7 3/0 85.0 7x3.93 AA 10.7 232.2 14.0
Anoli 85-A1F-18-10.7 3/0 85.0 18x2.45 A 10.7 233.9 15.7
Salarnaooer 107-A1F-7-12.1 4/0 107.0 7x4.41 AA 12.1 292.3 17.6
Clayman 107-A1F-18-12.1 4/0 107.0 18x2.75 A 12.1 294.7 19.2
Komodo 135-A1F-18-13.6 266.5 135.0 18x3.09 A 13.6 372.1 22.9
Dimensions and weights not designated as minimum or maximum are nominal values and subject to manufacturing tolerances.  In this context, weight means mass.
ASC, ALUMINUM CONDUCTOR, COMPACT-LAY-STRANDED (ELECTRICAL PROPERTIES)
CODE WORD
CONDUCTOR SIZE RESISTANCE (1) OHMSIKM AMPACITY @75'C (2) GEOMETRIC MEAN RADIUS CM
INDUCTIVE REACTANCE OHMIKM (3)
CAPACITIVE REACTANCE MEGAOHM-KM (3)
AWG OR kcmil mm2 DC @20'C
AC 025'C
AC @75'C
STANDARD E3X"'
Toad #6 13.3 2.148 2.191 2.625 93 99 0.162 0.3950 0.2368
Dragon #4 21.2 1.348 1.375 1.647 125 134 0.201 0.3786 0.2255
Moloch #2 33.6 0.8502 0.8675 1.039 166 180 0.256 0.3603 0.2146
Monitor #1 42.4 0.6738 0.6875 0.8236 192 209 0.283 0.3527 0.2094
Newt #1 42.4 0.6791 0.6930 0.8302 191 208 0.293 0.3504 0.2094
Tuatara 1/0 53.5 0.5340 0.5449 0.6528 222 243 0.320 0.3435 0.2038
Skink 1/0 53.5 0.5384 0.5494 0.6581 221 242 0.329 0.3416 0.2037
Alligator 2/0 67.4 0.4239 0.4326 0.5182 256 282 0.360 0.3347 0.1984
Gecko 2/0 67.4 0.4273 0.4362 0.5225 255 280 0.369 0.3330 0.1984
Crocodile 3/0 85.0 0.3361 0.3431 0.4109 297 327 0.402 0.3265 0.1928
Anoli 3/0 85.0 0.3389 0.3460 0.4144 295 326 0.411 0.3245 0.1929
Salamander 4/0 107.0 0.2670 0.2726 0.3265 343 380 0.454 0.3173 0.1872
Clayman 4/0 107.0 0.2692 0.2749 0.3293 341 379 0.463 0.3156 0.1873
Konnodo 266.5 135.0 0.2133 0.2181 0.2611 395 441 0.524 0.3064 0.1814

 

                                                                                                           

(1) Based on a conductivity of 61.0% lACS at 20"C for aluminum .

                                                                                                           
(2)  Based on a conductor temperature of 75°C at 60 Hz and the following conditions, 32°C ambient temperature, 1.98 ft/sec (0.6 m/sec) crosswind (90° to conductor), 0.5 coefficient of emissivity for a standard conductor and 0.9 for a E3X coated conductor, 0.5 coefficient of absorptivity for a standard conductor
and 0.2 for a E3X coated conductor, 42° northern latitude, sea level elevation, 90° azimuth of line (East-West), clear atmosphere, and a date and time of noon on July 1 (resulting in 95.0 W/ft² of solar and sky radiated heat). Actual ampacity will differ based on local conditions. For specific ampacities, contact your MVA Power sales representative.
(3) Values for inductive reactance and capacitive reactance are expressed in terms of a 1 ft radius (30.48 cm).