National : CSA C22.2 N° 38


DESCRIPTION


CSA File #LL23462 Class 5832 03

Compressed stranded (Class B) copper conductor with low temperature moisture resisting EXELENE® cross-linked polyethylene (XLPE) insulation, cabled without a ground wire. RoHS compliant.

Application

For open wiring and raceways (except cabletroughs and ventilated flexible cableway) in dry or wet locations, typically as feeder circuit cables in EMT.

Minimum recommended installation temperature minus 40°C (with suitable handling procedures).

Maximum conductor temperature 90°C.

INSTAGLIDE® reduced friction construction in sizes 6 AWG and larger, black and colours.

Construction

Conductor:

Bare, annealed copper conforming to ASTM B3 and Class B compressed stranded copper in accordance to ASTM B8, from 8 AWG to 3/0 AWG.

Insulation:

Coloured cross-linked polyethylene meeting the requirements for RW90 per CSA C22.2 No. 38.

Assembly:

Cabled without a ground wire.

Conductor Identification:

3 Conductors: Black, Red, Blue

4 Conductors: Black, Red, Blue, White

Characteristics

CONSTRUCTION CHARACTERISTICS
Conductor material Copper
ELECTRICAL CHARACTERISTICS  
Maximum operating voltage 600V
USAGE CHARACTERISTICS  
Maximum operating temperature 90°C

 

INSTAPLEX™ RW90 (–40°C) XLPE 600 V CABLED CONDUCTORS  
Part  Number Size  (AWG) No. Of  Conductors Insulation  Thickness Approximate  Overall Diameter Approximate  Net Cable  Weight  
 
 
mm inches mm inches kg/km lbs/kft  
604750 8 (7)  3 1.14 0.045 12.7 0.5 280 188  
604752 8 (7)  4 1.14 0.045 14.2 0.56 373 251  
604720 6 (7)  3 1.14 0.045 14.7 0.58 427 287  
604719 6 (7)  4 1.14 0.045 16.5 0.65 569 383  
604748 3 (7)  3 1.14 0.045 18.8 0.74 817 549  
604749 3 (7)  4 1.14 0.045 21.1 0.83 1091 733  
604754 3/0 (19)  3 1.4 0.055 30.2 1.2 2496 1677  
604755 3/0 (19)  4 1.4 0.055 34 1.34 3331 2238