Underground Distribution Cables. Jacketed Two-Conductor Parallel
STANDARDS
National : CSA C22.2 N° 52
DESCRIPTION
Compact stranded aluminum conductors
Black cross-linked polyethylene insulation with colour coded stripe
Full or reduced copper concentric neutral conductor
Black sunlight resistant PVC jacket
CSA C22.2 No.52
Characteristics | |||||
CONSTRUCTION CHARACTERISTICS | |||||
Conductor material | Aluminum | ||||
ELECTRICAL CHARACTERISTICS | |||||
Maximum operating voltage | 600V | ||||
USAGE CHARACTERISTICS | |||||
Maximum operating temperature | 90°C |
JACKETED USEB90 | |||||||||
Size (AWG/ Kcmil) | Insulation Thickness (mm) | Neutral Construction | Jacket Thickness (mm) | Approximate Overall Dimensions (mm) | Linear Mass (kg/km) | ||||
Full No. x Dia. | Reduced No. x Dia. | Full Neutral | Reduced | Full | Reduced | ||||
6 | 1.1 | 7 x 1.29 | 4 x 1.29 | 1.5 | 12.7 x 19.5 | 12.7 x 19.5 | 285 | 250 | |
4 | 1.1 | 10 x 1.29 | 6 x 1.29 | 2 | 14.9 x 22.8 | 14.9 x 22.8 | 440 | 390 | |
2 | 1.1 | 16 x 1.29 | 10 x 1.29 | 2 | 16.3 x 25.6 | 16.3 x 25.6 | 610 | 540 | |
1 | 1.4 | 20 x 1.29 | 12 x 1.29 | 2 | 17.7 x 28.4 | 17.7 x 28.4 | 760 | 660 | |
1/0 | 1.4 | 25 x 1.29 | 15 x 1.29 | 2 | 18.5 x 30.0 | 18.5 x 30.0 | 900 | 780 | |
2/0 | 1.4 | 20 x 1.63 | 19 x 1.29 | 2 | 20.2 x 32.8 | 19.6 x 32.2 | 1100 | 920 | |
3/0 | 1.4 | 25 x 1.63 | 24 x 1.29 | 2 | 21.4 x 35.2 | 20.8 x 34.4 | 1300 | 1120 | |
4/0 | 1.4 | 20 x 2.05 | 21 x 1.63 | 2 | 23.6 x 38.8 | 22.8 x 37.8 | 1600 | 1340 | |
250 | 1.7 | 25 x 2.05 | 23 x 1.63 | 2 | 25.4 x 42.2 | 24.6 x 41.4 | 1900 | 1600 | |
300 | 1.7 | 20 x 2.59 | 20 x 2.05 | 2.8 | 28.6 x 46.2 | 27.3 x 44.9 | 2390 | 2000 | |
350 | 1.7 | 24 x 2.59 | 25 x 2.05 | 2.8 | 30.4 x 49.6 | 29.4 x 48.6 | 2700 | 2250 | |
500 | 1.7 | 30 x 2.59 | 30 x 2.05 | 2.8 | 33.6 x 57.0 | 32.4 x 55.0 | 3650 | 3100 |