MVA  OH Duplex Neutral-Supported Cable Type NS75

600 V, Aluminum Conductor, LLDPE Insulation, ACSR Neutral

DUPLEX TYPE NS75- LLDPE- ACSR FULL SIZE NEUTRAL- 600 VOLTS
PHASE CONDUCTORS ACSR COMPACT BARE NEUTRAL OVERALL
SIZE (AWG) NO. OF WIRES COND. O.D. (mm) MIN.INS. THKN. (mm) NOM. INS. O.D. (mm) SIZE (AWG) NO. OF WIRES (A1/S1A) RATED STRENGTH kN (I) COND. O.D. (mm) EFFECTIVE O.D. (mm) APPROX. WEIGHT (kg/km) AMPACITY
(2)
6 7 4.29 1 04 6.63 6 6/1 5.18 5.0 12 111 80
4 7 5.41 1 04 7.75 4 6/1 8.14 6.4 14 169 105
2 7 6.88 1 04 9.14 2 6/1 12.4 8.1 17 260 140
1/0 7 8.53 1.37 11.6 1/0 6/1 18.9 10.1 22 412 185
(1)  Rated strengths are based on CAN/GSA C49.2 standard calculation method.
(2) Ampacity rating is per 20t5 CEC Table 36A, at 3o•c ambient, with sun-radiated heat energy oft 025 Wtm•, a wind speed of 0.6 m/s, and maximum conductor temperature of 75•c.
Dimensions and weights not designated minimum or maximum are nominal values and subject  to manufacturing tolerances. In this context, weight means mass.
TRIPLEX TYPE NS75- LLDPE- ACSR FULL SIZE NEUTRAL-600  VOLTS
PHASE CONDUCTORS ACSR COMPACT BARE NEUTRAL (4) OVERALL
SIZE (AWG OR kcmil) NO.OF WIRES (I) COND. O.D. (mm) MIN.INS. THKN. (mm) NOM.INS. O.D. (mm) SIZE (AWG OR kcmil) NO.OF WIRES (A1./S1A) RATED STRENGTH kN (2) COND. O.D. (mm) EFFECTIVE O.D. (mm) APPROX. WEIGHT (kg/km) AMPACITY
(3)
6 7 4.29 1 04 6.63 6 6/1 5.18 5.03 13 167 80
4 7 541 1 04 775 4 6/1 8.14 6.35 16 252 105
2 7 6.88 1 04 9.14 2 6/1 124 8.11 19 383 140
1/0 7 8.53 1.37 11.6 110 6/1 18.9 10.1 24 601 185
2/0 7 9.65 1.37 12.6 2/0 6/1 23.5 11.5 27 751 210
310 7 10.7 1.37 13.8 310 6/1 29.6 12.8 29 931 245
4/0 7 12.1 1.37 15.2 4/0 6/1 37.3 14.3 32 1157 280
266.8 19 13.6 1.83 17.7 266.8 26/7 50.1 16.3 38 1486 325
336.4 19 15.3 1.83 194 336.4 26/7 62.3 18.3 42 1844 375
397.5 19 16.7 1.83 20.8 397.5 26/7 71.6 19.9 45 2157 415
477 19 18.3 1.83 224 477 26/7 86.0 21.8 49 2565 460
TRIPLEX TYPE NS75- LLDPE - ACSR REDUCED SIZE NEUTRAL -600 VOLTS
PHASE CONDUCTORS ACSR COMPACT BARE NEUTRAL (4) OVERALL
SIZE (AWG OR kcmil) NO.OF WIRES (I) COND. O.D. (mm) MIN.INS. THKN. (mm) NOM.INS. O.D. (mm) SIZE (AWG OR kcmil) NO.OF WIRES (A1/S1A) RATED STRENGTH kN (2) COND. O.D. (mm) EFFECTIVE O.D. (mm) APPROX. WEIGHT (kg/km) AMPACITY
(3)
4 7 541 1 04 7.75 6 6/1 5.18 5.03 15 220 105
2 7 6.88 1 04 9.14 4 6/1 8.14 6.35 18 333 140
1/0 7 8.53 1.37 11.6 2 6/1 124 8.11 23 527 185
210 7 9.65 1.37 12.6 1 6/1 15.5 8.99 25 650 210
3/0 7 10.7 1.37 13.8 1/0 6/1 18.9 10.1 28 803 245
4/0 7 12.1 1.37 15.2 2/0 6/1 23.5 11.5 30 996 280
266.8 19 13.6 1.83 17.7 3/0 6/1 29.6 12.8 35 1282 325
3364 19 15.3 1.83 194 410 6/1 37.3 14.3 39 1588 375
397.5 19 16.7 1.83 20.8 266.8 26/7 50.1 16.3 42 1890 415
477 19 18.3 1.83 224 3364 26/7 62.3 18.3 46 2277 460
(1) For compact stranded  constructions, the number of wires may be reduced as follows:
19-Wire Constructions - 18 Wires Minimum
37-Wire Constructions- 35 Wires Minimum
(2) Rated strengths are based on CAN/GSA C49.2 and C61089 standard calculation method.
(3) Ampacity  rating is per 2015 CEC Table 36A, at3o•c ambient, with sun-radiated heat energy of 1025 W/m', a wind speed of 0.6 m/s, and maximum conductor temperature of 75•c.
(4) ACSR neutral conductors 266.8 kcmil and larger are concentric round  conductors per CAN/GSA C61089.
Dimensions and weights not designated minimum or maximum  are nominal values and subject  to manufacturing tolerances. In this context, weight means mass.

 

QUADRUPLEX TYPE NS75 - LLDPE - ACSR FULL SIZE NEUTRAL - 600 VOLTS
PHASE CONDUCTORS ACSR COMPACT  BARE NEUTRAL (4) OVERALL
SIZE (AWGOR kcmil) NO. OF WIRES (I) COND. O.D. (mm) MIN. IE. THKN. (mm) NOM. IE. O.D. (mm) SIZE (AWG OR kcmil) NO. OF WIRES (111/SIA) RATED STRENGTH kN (2) COND. O.D. (mm) EFFECTIVE O.D. (mm) APPROX. WEIGHT (kg/km) AMPACITY
(3)
6 7 4.29 1 04 6.63 6 6/1 5.18 503 15 224 70
4 7 5.41 1 04 7.75 4 6/1 8.14 6.35 18 335 95
2 7 6.81 1 04 9.14 2 6/1 12.4 8.11 21 507 125
1/0 7 8.53 1.37 11.6 1/0 6/1 18.9 10.1 27 803 165
2/0 7 9.65 1.37 12.6 2/0 6/1 23.5 11.5 30 991 190
3/0 7 10.7 1.37 13.8 3/0 6/1 29.6 12.8 33 1224 220
4/0 7 12.1 1.37 15.2 4/0 6/1 37.3 14.3 36 1519 255
266.8 19 13.6 1.83 17.7 266.8 26/7 50.1 16.3 42 1955 290
336.4 19 15.3 1.83 19.4 336.4 26/7 62.3 18.3 46 2421 335
397.5 19 16.7 1.83 20.8 397.5 26/7 71.6 19.9 50 2828 370
477 19 18.3 1.83 22.4 477 26/7 86.0 21.8 54 3359 415
(1) For compact stranded constructions, the number of wires may be reduced as follows:
19-Wire Constructions- 18 Wires Minimum                                                      
37-Wire Constructions- 35 Wires Minimum                                                    
(2) Rated strengths are based on CAN/CSA C49.2 and C61089 standard calculation method
(3) Ampacity rating is per 2015 CEC Table 36A, at 30°C ambient, with sun-radiated heat energy of 1025 W/m², a wind speed of 0.6 m/s, and maximum conductor temperature of 75°C.
(4) ACSR neutral conductors 266.8 kcmil and larger are concentric round conductors per CAN/CSA C61089.
 Dimensions and weights not designated minimum or maximum are nominal values and subject to manufacturing tolerances. In this context, weight means mass.

 

MVA OH Duplex Neutral-Supported Cable Type NS75/NS90

600 V, Aluminum Conductor, XLPE Insulation, ACSR Neutral

DUPLEX TYPE NS75JNS90- XLPE- ACSR FULL SIZE NEUTRAL- 600 VOLTS
PHASE CONDUCTORS ACSR COMPACT BARE NEUTRAL OVERALL
SIZE (AWG) NO.OF WIRES COND. O.D. (mm) MIN.INS. THKN. (mm) NOM. INS. O.D. (mm) SIZE (AWG) NO.OF WIRES (A1/S1A) RATED STRENGTH kN (I) COND. O.D. (mm) EFFECTIVE O.D. (mm) APPROX. WEIGHT (kg/km) AMPACITY (2)
6 7 4.29 1 04 6.63 6 6/1 5.18 5.0 12 111 95
4 7 541 1 04 7.75 4 6/1 8.14 64 14 169 125
2 7 6.88 1 04 9.14 2 6/1 12.4 8.1 17 260 165
1/0 7 8.53 1.37 11.6 1/0 6/1 18.9 10.1 22 412 220
1) Rated strengths are based on CAN/CSA C49.2 standard calculation method.
(2) Ampacity rating is per 2015 CEC Table 36A, at 30°C ambient, with sun-radiated heat energy of 1025 W/m², a wind speed of 0.6 m/s, and maximum conductor temperature of 90°C.
 Dimensions and weights not designated minimum or maximum are nominal values and subject to manufacturing tolerances. In this context, weight means mass.
TRIPLEX TYPE NS75/NSOO- XLPE- ACSR FULL SIZE NEUTRAL- &Xl VOLTS
PHASE CONDUCTORS ACSR COMPACT BARE NEUTRAL (4) OVERALL
SIZE (AWG OR kcmil) NO.OF WIRES (1)
COND. O.D. (m.m) MIN.INS. THKN. (mm) NOM.INS. O.D. (m.m) SIZE (AWG OR kcmil) NO.OF WIRES (A1/S1A) RATED STRENGTH kN (2) COND. O.D. (m.m) EFFECTIVE O.D. (m.m) APPIDX. WEIGHT (kg/km)
( lkni
AMPACITY
(3)
6 7 4.29 1 04 6.63 6 6/1 5.18 5 03 13 167 95
4 7 5.41 1 04 7.75 4 6/1 8.14 6.35 16 252 125
2 7 6.88 1 04 9.14 2 6/1 12.4 8.11 19 383 165
1/0 7 8.53 1.37 11.6 1/0 6/1 18.9 10.1 24 601 220
2/0 7 9.65 1.37 12.6 2/0 6/1 23.5 11.5 27 751 255
3/0 7 10.7 1.37 13.8 3/0 6/1 29.6 12.8 29 931 290
4/0 7 12.1 1.37 15.2 4/0 6/1 37.3 14.3 32 1157 335
266.8 19 13.6 1.83 17.7 266.8 26/7 50.1 16.3 38 1486 390
336.4 19 15.3 1.83 19.4 336.4 26/7 62.3 18.3 42 1844 450
397.5 19 16.7 1.83 20.8 397.5 26/7 71.6 19.9 45 2157 500
477 19 18.3 1.83 22.4 477 26/7 86.0 21.8 49 2565 560
TRIPLEX TYPE NS751NS90- XLPE- ACSR REDUCED SIZE NEUTRAL-600  VOLTS
PHASE CONDUCTORS ACSR COMPACT BARE NEUTRAL (4) OVERALL
SIZE (AWG OR kcmil) NO.OF WIRES (1) COND. O.D. (m.m) MIN.INS. THKN. (m.m) NOM.INS. O.D. (m.m) SIZE (AWG OR kcmil) NO.OF WIRES (A1/S1A) RATED STRENGTH kN (2) COND. O.D. (m.m) EFFECTIVE O.D. (m.m) APPIDX. WEIGHT (kg/km)
( lkni
AMPACITY
(3)
4 7 5.41 1 04 7.75 6 6/1 5.18 5 03 15 220 125
2 7 6.88 1 04 9.14 4 6/1 8.14 6.35 18 333 165
1/0 7 8.53 1.37 11.6 2 6/1 12.4 8.11 23 527 220
2/O 7 9.65 1.37 12.6 1 6/1 15.5 8.99 25 650 255
3/0 7 10.7 1.37 13.8 1/0 6/1 18.9 10.1 28 803 290
4/0 7 12.1 1.37 15.2 2/0 6/1 23.5 11.5 30 996 335
266.8 19 13.6 1.83 17.7 3/0 6/1 29.6 12.8 35 1282 390
336.4 19 15.3 1.83 19.4 4/0 6/1 37.3 14.3 39 1588 450
397.5 19 16.7 1 .83 20.8 266.8 26/7 50.1 16.3 42 1890 500
477 19 18.3 1.83 22.4 336.4 26/7 62.3 18.3 46 2277 560
(1) For compact stranded  constructions. the number  of wires may be reduced as follows:                                              
19-Wire Constructions - 18 Wires Minimum                                            
37-Wire Constructions- 35 Wires Minimum                                                    
(2) Rated strengths are based on CAN/GSA  061089 standard calculation method.                                                  
(3) Ampacity rating is per 2015 CEC Table 36A, at 30'C ambient, with sun-radiated heat energy of 1025 W/m2,   a wind speed of 0.6 m/s, and maximum conductor temperature  of 90'C.    
(4) ACSR neutral conductors 266.8 kcmil and larger are concentric round conductors per CAN/GSA 061089.                                        
 Dimensions and weights not designated minimum or maximum are nominal values and subject to manufacturing tolerances. In this context, weight means mass.

 

QUADRUPLEX TYPE NS75/NS90- XLPE - ACSR FULL SIZE NEUTRAL - 600 VOLTS
PHASE CONDUCTORS ACSR COMPACT BARE NEUTRAL (4) OVERALL
SIZE (AWG OR kcmil) NO.OF WIRES (1) COND. O.D. (mm) MIN.INS. THKN. (mm) NOM.INS. O.D. (mm) SIZE (AWG OR kcmil) NO.OF WIRES (A1/S1A) RATED STRENGTH kN (2) COND. O.D. (mm) EFFECTIVE O.D. (mm) APPROX. WEIGHT (kg/km) AMPACITY
(3)
6 7 4.29 1 04 6.63 6 6/1 5.18 503 15 224 85
4 7 5.41 1 04 7.75 4 6/1 8.14 6.35 18 335 110
2 7 6.81 1 04 9.14 2 6/1 12.4 8.11 21 507 150
1/0 7 8.53 1.37 11.6 1/0 6/1 18.9 10.1 27 803 200
2/0 7 9.65 1.37 12.6 2/0 6/1 23.5 11.5 30 991 230
3/0 7 10.7 1.37 13.8 3/0 6/1 29.6 12.8 33 1224 265
4/0 7 12.1 1.37 15.2 4/0 6/1 37.3 14.3 36 1519 305
266.8 19 13.6 1.83 17.7 266.8 26/7 50.1 16.3 42 1955 355
336.4 19 15.3 1.83 19.4 336.4 26/7 62.3 18.3 46 2421 410
397.5 19 16.7 1.83 20.8 397.5 26/7 71.6 19.9 50 2828 455
477 19 18.3 1.83 22.4 477 26/7 86.0 21.8 54 3359 510
(1) For compact  stranded constructions, the number of wires may be reduced as follows:                                              
19-Wire Constructions - 18 Wires Minimum                                            
37-Wire Constructions- 35 Wires Minimum                                                    
(2) Rated strengths are based on CAN/GSA C61089 standard calculation method.                                                    
(3) Ampacity rating is per 2015 CEC Table 36A, at 3 o•c ambient, with sun-radiated heat energy of 1025 W/m•2, a wind speed of 0.6 m/s, and maximum conductor temperature  of 90'C.
(4) ACSR neutral conductors 266.8 kcmil and larger are concentric round conductors per CAN/GSA C61089.                                        
Dimensions and weights not designated minimum or maximum are nominal values and subject to manu1acturing tolerances. In this context, weight means mass.