PVC Insulated Nylon Covered Cables
STANDARDS
National : CSA C22.2 N° 75
DESCRIPTION
CSA File #LL23462 Class 5832 02
U.L. Standard #83 - U.L. Approval # E70347
Single copper conductor with thin wall PVC insulation and nylon covering with FT1 rating. Rated 600 volts. LEAD FREE.
INSTAGLIDE® reduced friction construction in sizes 6 AWG and larger.
APPLICATION
General purpose building wire for installation as exposed or concealed wiring and in raceways (except cable trays) in dry or damp locations.
Minimum recommended installation temperature minus 10°C (with suitable handling procedures).
Maximum conductor temperature 90°C dry, 75°C in wet locations, and 60°C when exposed to oil.
Approved for use with ceiling fixtures.
INSTAGLIDE® reduced friction construction in sizes 6 AWG and larger.
Harmonized Product Print Legend:
E53058 F INSTAGLIDE® 2/0 AWG (67.4mm²) (UL) THHN OR THWN-2 OR GR II OR MTW 600 VOLT VW-1 CT USE MADE IN CANADA LL 23462 2/0 AWG CSA/ACNOR T90 / TWN75 NYLON FT1
Characteristics
CONSTRUCTION CHARACTERISTICS | |||||
Conductor material | Copper | ||||
ELECTRICAL CHARACTERISTICS | |||||
Maximum operating voltage | 600V | ||||
USAGE CHARACTERISTICS | |||||
Maximum operating temperature | 90°C |
INSTAGLIDE® T90 NYLON / TWN75 | ||||||||||||||
Size AWG or kcmil |
Insulation Thickness | Nylon Thickness | Approximate Diameter | Approx. Net Cable Weight | Ampacity (amps at 30°C Ambient) | Where exposed to oil Conduit # | ||||||||
Damp & Dry | Wet | |||||||||||||
mm | in | mm | in | mm | in | kg/km | lbs/kft | Free Air | Conduit # | Free Air | Conduit # | |||
14 (1) | 0.38 | 0.015 | 0.1 | 0.004 | 2.7 | 0.11 | 25 | 15 | 20 | 15 | 20 | 15 | 15 | |
12 (1) | 0.38 | 0.015 | 0.1 | 0.004 | 3.1 | 0.12 | 35 | 23 | 25 | 20 | 25 | 20 | 20 | |
10 (1) | 0.51 | 0.02 | 0.1 | 0.004 | 3.9 | 0.15 | 55 | 37 | 40 | 30 | 40 | 30 | 30 | |
14 (19) | 0.38 | 0.015 | 0.1 | 0.004 | 2.8 | 0.11 | 24 | 16 | 20 | 15 | 20 | 15 | 15 | |
12 (19) | 0.38 | 0.015 | 0.1 | 0.004 | 3.3 | 0.13 | 36 | 24 | 25 | 20 | 25 | 20 | 20 | |
10 (19) | 0.51 | 0.02 | 0.1 | 0.004 | 4.2 | 0.17 | 58 | 39 | 40 | 30 | 40 | 30 | 30 | |
8 (19) | 0.76 | 0.03 | 0.13 | 0.005 | 5.5 | 0.22 | 96 | 65 | 70 | 45 | 65 | 45 | 40 | |
6 (19) | 0.76 | 0.03 | 0.13 | 0.005 | 6.5 | 0.26 | 146 | 98 | 100 | 65 | 95 | 65 | 55 | |
4 (19) | 1.02 | 0.04 | 0.15 | 0.006 | 8.3 | 0.33 | 233 | 157 | 135 | 85 | 125 | 85 | 70 | |
3 (19) | 1.02 | 0.04 | 0.15 | 0.006 | 9 | 0.36 | 288 | 193 | 155 | 105 | 145 | 100 | 80 | |
2 (19) | 1.02 | 0.04 | 0.15 | 0.006 | 9.8 | 0.39 | 357 | 240 | 180 | 120 | 170 | 115 | 100 | |
1 (19) | 1.27 | 0.05 | 0.18 | 0.007 | 10.9 | 0.43 | 446 | 300 | 210 | 140 | 195 | 130 | 110 | |
1/0 (19) | 1.27 | 0.05 | 0.18 | 0.007 | 11.8 | 0.47 | 555 | 373 | 245 | 155 | 230 | 150 | 125 | |
2/0 (19) | 1.27 | 0.05 | 0.18 | 0.007 | 12.9 | 0.51 | 698 | 470 | 285 | 185** | 265 | 175 | 145 | |
3/0 (19) | 1.27 | 0.05 | 0.18 | 0.007 | 14.2 | 0.56 | 862 | 579 | 330 | 210 | 310 | 200 | 165 | |
4/0 (19) | 1.27 | 0.05 | 0.18 | 0.007 | 15.5 | 0.61 | 1077 | 724 | 385 | 235 | 360 | 230 | 195 | |
250 (37) | 1.52 | 0.06 | 0.2 | 0.008 | 17.2 | 0.68 | 1272 | 855 | 425 | 265 | 405 | 255 | 215 | |
300 (37) | 1.52 | 0.06 | 0.2 | 0.008 | 18.5 | 0.73 | 1521 | 1022 | 480 | 295 | 445 | 285 | 240 | |
350 (37) | 1.52 | 0.06 | 0.2 | 0.008 | 19.7 | 0.78 | 1762 | 1184 | 530 | 325 | 505 | 310 | 260 | |
400 (37) | 1.52 | 0.06 | 0.2 | 0.008 | 20.8 | 0.82 | 2002 | 1345 | 575 | 345 | 545 | 335 | 280 | |
500 (37) | 1.52 | 0.06 | 0.2 | 0.008 | 22.9 | 0.9 | 2482 | 1668 | 660 | 395 | 620 | 380 | 320 | |
**For 3-wire 120/240 and 120/208V residential services or sub-services, the allowable ampacity | ||||||||||||||
for #2/0 AWG copper shall be 200 amperes. In these cases, the 5% adjustment per C.E. Code Rule 8-106(1) cannot be applied. | ||||||||||||||
#Based on not more than 3 copper conductors in raceway or cable. |